Chapter 9

Troubleshooting

252

Alarm

Code

Alarm

Level

Alarm Name

Cause/Treatment

0C6

Torque current

• Mismatching force feed

back

Cause

: The feedback from the loadcell has continuously

been larger than the rating motor output for 256 ms

or longer.

Treatment : 1) Check that there is no external force applied in

the direction to push back from the load side.

2) Review wiring of actuator and loadcell cables.

3) The actuator, controller or loadcell may be faulty.

Please contact IAI.

0C8

Overcurrent

Cause

: The output current in the power circuit section is

increased abnormally.

Treatment : This alarm will not be generated in normal

operation. If it occurs, insulation of the motor coil

may have deteriorated.

Check if there is deterioration in the insulation by

measuring the phase resistance between the

monitor connection lines U, V and W. The values for

the phase resistance should be almost the same.

There is a concern the insulation is deteriorated if

the values are different in large amount. Please

contact IAI.

0CA

Overheat

Cause

: This indicates overheat (95�C or more) of the

components inside the controller.

1) Operation is performed with the load condition

exceeding the specified range.

2) High temperature around the controller.

3) Load to the motor is high due to external force.

4) A faulty part inside the controller.

Treatment : 1) Revise the operation condition such as

decreasing the acceleration/deceleration speed.

2) Lower the ambient temperature of the controller.

3) Confirm that there is no error in the mechanical

part assembly condition.

(Note) This error would not normally occur. If it occurs, confirm

there is not (1) or (2) above. If the same error is issued

again even after confirming (1) or (2) is not in the

condition, it is considered to be a malfunction. Please

contact IAI.

0CB

Current sensor offset

adjustment error

Cause

: An error was found to the sensor in the status check

of the current detection sensor conducted at the

initializing process in the startup.

1) The current detection sensor or any of its

surrounding parts is faulty.

2) Inappropriate offset adjustment

Treatment : A work (PC board) change or offset adjustment is

required.

Please contact IAI.

0CD

Emergency-stop relay

Cause

: A melt-down of the emergency stop relay inside the

controller.

Treatment : The relay or controller must be replaced.

Please contact IAI.

0CE

Cold start

Drop in control supply

voltage

Cause

: 1) The AC power supply voltage is low.

2) Faulty part inside the controller

Treatment : Check the voltage of the input power supply.

In the case that the voltage is normal, please

contact IAI.