12. PLC Timer Setting

Do not have the PLC timer setting to be done with the minimum setting.

Setting to “1” for 100msec timer turns ON at the timing from 0 to 100msec while 10msec timer

from 0 to 10msec for some PLC.

Therefore, the same process as when the timer is not set is held and may cause a failure such

as the actuator cannot get positioned to the indicated position number in Positioner Mode.

Set “2” as the minimum value for the setting of 10msec timer and when setting to 100msec, use

10msec timer and set to “10”.

International Standards Compliances

SCON-CA comply with the following international standards:

Refer to Overseas Standard Compliance Manual (ME0287) for more detailed information.

RoHS Directive

CE Marking

UL

Except for MECHATROLINK Connection Type

UL

1. Use Environment

• For use in pollution degree 2 environment

• Maximum surrounding air temperature rating, 40�C ;

2. Solid State Motor Overload Protection

Solid state motor overload protection is provided at 115% of full-load current

3. Short Circuit Current Rating�SCCR�

Models SCON-X-XXX-X-X-2-X-X “Suitable for use on a circuit capable of delivering not more

than 5,000 rms amperes, 240V AC maximum”

Models SCON-X-XXX-X-X-1-X-X “Suitable for use on a circuit capable of delivering not more

than 5,000 rms amperes, 120V AC maximum”

4. Branch Circuit Protection

Integral solid state short circuit protection does not provide branch circuit protection. Branch

circuit protection must be provided in accordance with the National Electric Code and any

additional local codes.

5. Risk of Electric Shock

Do not touch terminals within 10 minutes after disconnect the power. Risk of electric shock.