IAI America SCON-CA User Manual

Page 83

Advertising
background image

Chapter 2 Wiring

73

[3] Pulse converter : AK-04

The pulse converter converts command pulses in the open collector mode to those in the

differential mode.

Use this converter if the host controller sends output pulses in the open collector mode.

Host Controller

(PLC etc.)

SCON-CA

e-CON Connector

37104-3122-000FL (3M or equivalent)

e-CON Connector

37104-3122-000FL (3M or equivalent)

Caution

1) Pay attention not to insert wrongly because it is the same e-CON connector as

input and output. Putting the power on with the insertion being wrong will burn

AK-04.

2) Use the pulse converter in the ambient temperature range between 0ºC and 40ºC.

3) The temperature increase of about 30ºC occurs during operation. Accordingly,

neither install several pulse converters in close contact nor install them within a

duct. Do not install the pulse converter near other heating devices.

4) If more than one pulse converters are installed, set a pulse converter apart from another

by 10mm or more.

5) Make the wiring between the host controller (PLC, etc.) and AK-04 as short as possible.

Long one is easy to pick the noise. Also make the wiring between AK-04 to SCON-CA

as short as possible.

Place AK-04 close to the host controller.

A recommended installation sample is shown in the figure below.

Make the cable length between the host controller and pulse converter as short as possible.

Wiring length :

50mm or shorter recommended

Host Controller

Keep pulse converters separated for 10mm or more from each other.

10mm or more

10mm or more

If this installation cannot be

avoided, shorten the length of

the wiring with the host

controller as much as possible.

Advertising