Chapter 3 Operation

115

Control method

This is a function to detect whether the specified load is applied to the actuator by checking the

torque while in press-fitting operation when having a press-fitting process with the pressing

operation. If there is no resistance in press-fitting, the specified load would not be applied, thus

it is defined as the normal pressing is not conducted and an alarm can be issued from PLC.

It monitors the pressing force set in % in “Threshold” in the position data, and turns the torque

level status (TRQS) signal ON when the pressing force reaches the following condition. At the

same time, load output judge (LOAD) signal also turns ON if it is in the position zone.

This signal turns OFF either when a movement command to another position is issued or the

servo is turned OFF. This signal is kept ON once it is turned ON until the next movement

command.

Condition:

(Total time of pressing force to reach above threshold) – (total time of pressing force to get

below threshold) � 255ms (Parameter No.6)

265ms

110ms + 5ms + 10ms - 5ms + 135ms ≥ 255ms

Load output judgment (TRQS output)

TRQS

LOAD

Pressing Force

Push [%]

Threshold [%]

Time

ms

ms

ms

5

10

5

110ms

135ms

Position zone

Pressing force exceeding

force judgment margin is

occurred

Pressing force being

dropped below threshold

Positive side of force judgment margin

Negative side of force judgment margin

Touched to work