Chapter 9

Troubleshooting

240

[Startup Adjustment with Teaching Tool when Control Circuit Incomplete]

Situation

Possible cause

Check/Treatment

Operation is not

performed even though

the teaching tool is

connected, and power to

the controller motor and

control circuit is

supplied.

(the emergency stop

switch is released on the

teaching pendant)

Cable treatment or mode selection

1) Emergency stop condition

The status display LED EMG is

ON.

It is not connected between

EMG + and -.

2) Servo OFF condition

3) In pause

1) Make a short circuit between

EMG + and -.

Warning

If the process of 1) is conducted, put

back the setting as soon as the

adjustment work is finished.

Starting the operation without

putting it back may cause a serious

accident since the emergency stop

is set invalid.

2) 3) Put the operation mode switch on

the front panel of the controller to

“MANU” side, and select the teach

mode on the teaching tool.