Chapter 8 I/O Parameter

217

[58] Timer period for emergency stop relay fusing monitor (Parameter No.72)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

72 Timer period for emergency

stop relay fusing monitor

EMWT

msec

0 to 60000

3000

This parameter defines the timer period in which fusing of the emergency stop relay for cutting

off the motor drive power is detected.

If the motor AC power is not cut off after elapse of the timer period set by this parameter

following the cutoff of the driver power, the control will recognize that the relay has been fused

and generate an alarm.

Normally this parameter need not be changed. When a value between 0 and 9 is set, no fusing

is detected.

[59] Encoder voltage level (Parameter No.73)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

73 Encoder voltage level

EVLV

0 to 3

Depending on

encoder cable length

To stabilize encoder detection signals, this parameter defines the voltage supplied to the

encoder circuit to one of four levels in accordance with the encoder type and the length of the

encoder relay cable.

Normally this parameter need not be changed. If you have changed the length of the encoder

relay cable after the shipment, the value of the parameter may be changed.

If you wish to change this parameter, always consult us in advance. If the setting is not optimum,

it may cause an operation error of the actuator or malfunction of the encoder.

[60] PIO Power Supply Supervision (Parameter No.74)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

74 PIO Power Supply Supervision

(Note1)

FPIO

0: Enabled

1: Disabled

0

A power monitor function is provided to prevent incorrect operations, burning of the I/O board

and/or breakdown of parts caused by an abnormal voltage of the 24V DC for PIO power supply.

This parameter can be disabled in certain situations such as when the controller is operated by

a teaching tool without connection of PIO during trail operation for adjustments. Do not forget

put it back to “0” (Valid) before starting the system operation after the test run for the adjustment

is finished.

Set Value

Description

0

Enabled

1

Disabled

Note 1 The power monitoring will not be conducted no matter the settings for the Fieldbus

types (CC-Link/DeviceNet, etc.).