Chapter 8 I/O Parameter

202

[6] Default velocity (Parameter No.8)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

8

Default velocity

VCMD

mm/s

(deg/s)

1 to Actuator’s max.

verocity

Rated actuator

speed

The factory setting is the rated velocity of the actuator.

When a target position is set in an unregistered position table, the setting in this parameter is

automatically written in the applicable position number.

It is convenient to set the velocity often used.

[7] Default acceleration/deceleration (Parameter No.9)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

9

Default

acceleration/deceleration

ACMD

G

0.01 to actuator's

max. acceleration/

deceleration

Rated actuator's

acceleration/

deceleration

The factory setting is the rated acceleration/deceleration of the actuator.

When a target position is set in an unregistered position table, the setting in this parameter is

automatically written in the applicable position number.

It is convenient to set the acceleration/deceleration often used.

[8] Default positioning width (in-position) (Parameter No.10)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

10 Default positioning width

INP

mm

(deg)

0.01 to 999.99

0.10

When a target position is set in an unregistered position table, the setting in this parameter is

automatically written in the applicable position number. When the remaining moving distance

enters into this width, the positioning complete signal is output.

It is convenient to set the positioning width often used.

[9] Current-limiting value during home return (Parameter No.13)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

13 Current-limiting value during

home return

ODPW

%

1 to 300

In accordance with

actuator

The factory setting conforms to the standard specification of the actuator.

Increasing this setting will increase the home return torque.

Normally this parameter need not be changed. If the home return should be completed before

the correct position depending on the affixing method, load condition or other factors when the

actuator is used in a vertical application, the setting value must be increased. Please contact

IAI.