Chapter 8 I/O Parameter

207

[21] PIO jog velocity (Parameter No.26), PIO jog velocity 2 (Parameter No.47)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

26 PIO jog velocity

IOJV

mm/s

(deg/s)

1 to Actuator’s

max. speed

(note1)

100

This is the jog operation velocity setting with PIO signal (jog input command) when PIO pattern

= 1 (Teaching Mode) is selected.

Set an appropriate value in Parameter No.26 in accordance with the purpose of use.

Note 1 The maximum speed is limited to 250mm/s.

[22] Movement Command Type (Parameter No.27)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

27 Movement Command Type

FPIO

0 : Level

1 : Edge

0

Set the input methods for the start signal (ST0 to ST6, or ST0 to ST2 if PIO Pattern = 5) when

PIO Pattern 4 = Electromagnetic Valve Mode 1 (7-point type), PIO Pattern 5 = Electromagnetic

Valve Mode 2 (3-point type) and PIO Pattern 7 = Pressing Operation Using Force Sensor Mode

2 (Electromagnetic Valve Mode).

Set Value

Input method

Description

0

Level

The actuator starts moving when the input signal turns ON.

When the signal turns OFF during movement, the actuator will

decelerate to a stop and complete its operation.

1

Edge

The actuator starts moving when the rising edge of the input

signal is detected. The actuator will not stop when the signal

turns OFF during the movement, until the target position is

reached.

[Level System]

Move command input

(ST0 to ST6)

Movement complete

(PE0 to PE6)

Actuator movement

Stop

Target Position

[Edge System]

Move command input

(ST0 to ST6)

Movement complete

(PE0 to PE6)

Actuator movement

Target Position