Yokogawa Integral Oxygen Analyzer ZR202 User Manual

Page 173

Advertising
background image

<12. Troubleshooting>

12-3

IM 11M12A01-02E

8th Edition : Jan.13,2012-00

12.1.2.2 Error2: Heater Temperature Failure

This error occurs if the detector heater temperature does not rise during warm-up, falls below 730

°C after warm-up, or exceeds 780 °C. When Error2 occurs, Alarm 10 (cold junction temperature

alarm) or Alarm 11 (thermocouple voltage alarm) may be generated at the same time. Be sure to

press the error indication to get the error description and confirm whether or not these alarms are

being generated simultaneously.
If Alarm 10 is generated simultaneously, a failure in the cold junction system on the detector

terminal block is suspected. In this case, follow the procedure according to troubleshooting for

Alarm 10 in Section 12.2.2.5.
If Alarm 11 is generated simultaneously, a failure in the thermocouple system located in the

detector heater is suspected. In this case, follow the procedure according to troubleshooting for

Alarm 11 in Section 12.2.2.6
If this failure occurs immediately after the power is supplied, the polarity at thermocouple input

connection (TC+, TC-) on the converter may be reversed. Check the connection from the

detector.
Causes considered for cases where Error2 occurs independently are shown below.
(1) Faulty heater in the detector (heater wire breakage)
(2) Faulty thermocouple in the detector
(3) Faulty cold junction sensor located at the detector terminal block.
(4) Failure in electrical circuits inside the converter
(5) Heater temperature control overcurrent limiting triggered.
(6) TC+ ,TC- thermocouple terminals wired to detector with reverse (wrong) polarity.

Overcurrent protection is triggered if there are problems in the heater wiring. When the protective

circuit is triggered, the internal fuse blows and the heater is disconnected, resulting in Error 2

(temperature failure).

<Locating cause of failure, and countermeasures>
(1) Turn off power to the converter.
(2) Remove the cable from terminals 7 and 8 of the detector and measure the resistance value

between these terminals. The heater unit is normal if the resistance is lower than about

90 Ω. If the resistance value is higher, failure of the heater unit is suspected. In this case,

replace the heater unit (refer to Section 11.1.3, Replacement of the Heater Unit). In addition,

check that the wiring resistance between the converter and detector is 10 Ω or less.

(3) Ensure that TC+ terminal (terminal 3 in detector) is connected to converter TC+ terminal,

and TC- terminal (terminal 4) is connected to converter TC- terminal.

(4) Remove the wiring from terminals 3 and 4 of the detector and measure the resistance

value between these terminals. The thermocouple is considered normal if the resistance

value is 5 Ω or less. If the value is higher than 5 Ω, it may indicate that the thermocouple

wire has broken or is about to break. In this case, replace the heater unit (refer to Section

11.1.3, Replacement of the Heater Unit). Also, check that the wiring resistance between the

converter and detector is 10 Ω or less.

(5) Even if items (2) to (4) are normal, the heater overcurrent protection fuse may have blown.

Check for wiring problems such as the following:

1) Heater terminals shorted.

2) Heater terminal(s) shorted to ground.

3) Heater terminals shorted to power supply.

If the internal fuse blows, this cannot be replaced by the user. Contact your Yokogawa service

representative.

Advertising
This manual is related to the following products: