1-2 Overview

865-UM001A-EN-P – July 2009

Freely configurable interlocking schemes with basic logic
functions

Recording of events and fault values into an event register from
which the data can be read via a keypad and a local HMI or by
means of a PC based SetPointPS user interface

Latest events and indications are in non-volatile memory.

Easy configuration, parameter setting and reading of information
via local HMI, or with the SetPointPS programming software

Easy connection to power plant automation system due to a
versatile serial connection and several available communication
protocols

Built-in, self-regulating ac/dc converter for auxiliary power
supply from any source within the range from 40 to 865 V dc or
ac. The alternative power supply is for 18 to 36 V dc

Built-in disturbance recorder for evaluating all the analogue and
digital signals

Eight (8) programmable stages for alarming or protection
purposes

The Allen-Bradley 865 differential protection relay is ideal for
transformer, motor, generator and short cable (100) differential
protection. The relay features the following protection functions.

Table 1-1 – List of Protection Functions

IEEE/

ANSI code

IEC symbol

Function name

50/51

3I>, 3I>>, 3I’>, 3I’>>

Overcurrent protection

87

∆I>, ∆I>>

Differential overcurrent protection

46 I

2

>, I’

2

> Current

unbalance

protection

49

T>

Thermal overload protection

50N/51N

I

0

>,

I

0

>>,

I

0

>>>,

I

0

>>>>

Earth fault protection

50BF

CBFP

Circuit-breaker failure protection

99 Prg1...8

Programmable

stages

50ARC

50NARC

ArcI>, ArcI’>

ArcI

01

>, ArcI

02

>

Optional arc fault protection

Further the relay includes a disturbance recorder. Arc protection
is optionally available.


The relay communicates with other systems using common
protocols, such as the Modbus RTU, ModbusTCP, Profibus DP,
Ethernet, DeviceNet, IEC 60870-5-103, SPA bus and DNP 3.0,
IEC 61850 and IEC 60870-5-101.