Binary

Output

The binary output (BO) on the arc option card (see Chapter 8) can be
used to give the light indication signal or any other signal or signals
to another relay's binary input to build selective arc protection
systems. Selection of the BO connected signal(s) is done with the
output matrix (See Chapter 5). BO is an internally wetted 48 Vdc
signal for BI of other Allen-Bradley relays or dedicated arc
protection devices by Allen-Bradley.

Delayed Light Indication Signal

There is a delayed light indication output signal available for
building selective arc protection systems. Any light source
combination and a delay can be configured. The resulting signal is
available in the output matrix to be connected to BO, output relays
etc.

Pick Up Scaling

The per unit (pu) values for pick up setting are based on the current
transformer values.

ArcI>:

1 pu = 1xI

N

= rated phase current CT value

ArcI’>:

1 pu = 1xI’

N

= rated phase current CT value

ArcI

01

>:

1 pu = 1xI

01N

= rated residual current CT value

for input I

01

ArcI

02

>:

1 pu = 1xI

02N

= rated residual current CT value

for input I

02

Table 3.17 – Parameters of Arc Protection Stages Arcl>, Arcl’>, Arcl

01

A,

Arcl

02

> (50 ARC / 50N ARC)

Parameter

Value

Unit

Description

Note

Status –

Start
Trip

Current status of the stage
Light detected according ArcIn
Light and overcurrent detected

F
F

LCntr

Cumulative light indication counter. S1,
S2 or BI.

C

SCntr

Cumulative light indication counter for
the selected inputs according parameter
ArcIn

C

TCntr

Cumulative

trip

counter

C

Force Off

On

Force flag for status forcing for test
purposes. This is a common flag for all
stages and output relays, too.
Automatically reset by a 5-minute
timeout.

Set


ILmax
I’Lmax
Io1
Io2

Value of the supervised signal
Stage ArcI>
Stage ArcI’>
Stage ArcI

01

>

Stage ArcI

02

>