Chapter 10 – technical data, Connections, Measuring circuitry – Rockwell Automation 865 Differential Protection Relay User Manual

Page 171: Auxiliary voltage, Technical data, Chapter

Advertising
background image

Chapter

10

865-UM001A-EN-P – July 2009



Technical

Data


Table 10.1 – Measuring Circuitry

Rated phase current

5 A (configurable for CT secondaries 1 – 10 A)

- Current measuring range

0…250 A

- Thermal withstand

20 A (continuously)

100 A (for 10 s)

500 A (for 1 s)

- Burden

< 0.2 VA

Rated phase current

1 A (configurable for CT secondaries 1 – 10 A)

- Current measuring range

0…50 A

- Thermal withstand

20 A (continuously)

100 A (for 10 s)

500 A (for 1 s)

- Burden

< 0.1 VA

Rated residual current (optional)

5 A (configurable for CT secondaries 1 – 10 A)

- Current measuring range

0…25 A

- Thermal withstand

20 A (continuously)

100 A (for 10 s)

500 A (for 1 s)

- Burden

< 0.2 VA

Rated residual current

1 A (configurable for CT secondaries 0.1 – 10 A)

- Current measuring range

0…5 A

- Thermal withstand

4 A (continuously)

20 A (for 10 s)

100 A (for 1 s)

- Burden

< 0.1 VA

Rated frequency f

n

45 – 65 Hz

- Frequency measuring range

16 – 75 Hz

Terminal block:

Maximum wire dimension:

- Solid or stranded wire

4 mm

2

(10-12 AWG)

Table 10.2 – Auxiliary Voltage

Catalog No./ Option

Type A (standard)

Type B (option)

Rated voltage Uaux

40 - 865 V ac/dc

18...36 V dc

110/120/220/240 V ac

24 V dc

48/60/110/125/220 V dc

Power consumption

< 7 W (normal conditions)

< 15 W (output relays activated)

Max. permitted interruption time

< 50 ms (110 V dc)

Terminal Block:

Max. wire dimension:

- Phoenix MVSTBW or equivalent

2.5 mm

2

(13-14 AWG)