3-10 Protection

Functions

865-UM001A-EN-P – July 2009

The stage also includes second harmonics blocking. The second
harmonic is calculated from winding currents. Harmonic ratio is:

100

x

I

f2_Winding

/ I

f1_Winding

[%]


Fast differential overcurrent stage ΔI>> does not include slope
characteristics and second harmonics blocking.

Parameters of the Differential Overcurrent Stages

Table 3.4 – Parameters of the Differential Overcurrent Stages ΔI> (87)

Parameter

Value/unit

Measured values

ΔL1
ΔL2
ΔL3

xIn

Current difference value

ΔI> %ln

Setting

value

Slope1

%

Slope 1 setting

Ibias2

xIn

Bias current start of slope 2

Slope2

%

Slope 2 setting

Harm2>

On/Off

2. harmonic blocking enable/disable

Setting values

Harm2>

%

2. harmonic block limit

TCntr

Cumulative trip counter

1-N, 2-N, 3-N

Fault type/single-phase fault e.g.: 1-N = fault on phase L1

1-2, 2-3, 1-3

Fault type/two-phase fault e.g.: 2-3 = fault between L2 and L3

Type

1-2-3

Fault type/three-phase fault

ΔFlt

xIn

Max. value of fault differential current as compared to I

n

Bias

xIn

Value of bias current of faulted phase as compared to I

n

Recorded values

Load

xIn

1 s mean value of pre-fault phase currents IL1…IL3

Measurement ranges are described under “Measuring Circuitry” in Chapter 10.
Setting ranges are described in Table 10.15 and Table 10.16, Chapter 10.


Table 3.5 – Parameters of the Differential Overcurrent Stages ΔI>> (87)

Parameter

Value/unit

Measured values

ΔL1
ΔL2
ΔL3

xIn

Current difference value

Setting values

ΔI>>

xIn

Setting value

TCntr

Cumulative

trip

counter

1-N, 2-N, 3-N

Fault type/single-phase fault e.g.: 1-N = fault on phase L1

1-2, 2-3, 1-3

Fault type/two-phase fault e.g.: 2-3 = fault between L2 and L3

Type

1-2-3

Fault type/three-phase fault

ΔFlt

xIn

Max. value of fault differential current as compared to I

n

Recorded values

Load

xIn

1 s mean value of pre-fault phase currents IL1…IL3