Clearing "operations left" counters, Operations counter to monitor the wearing, Logarithmic interpolation – Rockwell Automation 865 Differential Protection Relay User Manual

Page 100

Advertising
background image



4-8 Supporting

Functions

865-UM001A-EN-P – July 2009


Any actual interrupted current will be logarithmically weighted for
the two given alarm current levels and the number of operations left
at the alarm points is decreased accordingly. When the "operations
left" i.e. the number of remaining operations, goes under the given
alarm limit, an alarm signal is issued to the output matrix. Also an
event is generated depending on the event enabling.

Clearing "Operations Left" Counters

After the breaker curve table is filled and the alarm currents are
defined, the wearing function can be initialized by clearing the
decreasing operation counters with parameter "Clear" (Clear oper.
left cntrs). After clearing the relay will show the maximum allowed
operations for the defined alarm current levels.

Operation Counters to Monitor the Wearing

The operations left can be read from the counters "Al1Ln" (Alarm 1)
and "Al2Ln" (Alarm2). There are three values for both alarms, one
for each phase. The smallest of three is supervised by the two alarm
functions.

Logarithmic

Interpolation

The permitted number of operations for currents in between the
defined points is logarithmically interpolated using equation

Equation 4.1

n

I

a

C =

,

where

C = permitted operations
I = interrupted current
a = constant according Equation 4.2
n = constant according Equation 4.2

Equation 4.2

k

k

k

k

I

I

C

C

n

1

1

ln

ln

+

+

=

Equation 4.3

2

k

k

I

C

a =

ln

= natural logarithm function

C

k

= permitted operations. k = row 2...7 in Table 4.7.

I

k

= corresponding current. k = row 2...7 in Table 4.7.

C

k+1

= permitted operations. k = row 2...7 in Table 4.7.

I

k+1

= corresponding current. k = row 2...7 in Table 4.7.

Advertising