Chapter 3 – protection functions, Max. no. of protection stages in one applications, Protection functions – Rockwell Automation 865 Differential Protection Relay User Manual

Page 45: General features of protection stages, Setting groups, Chapter

Advertising
background image

Chapter

3

865-UM001A-EN-P – July 2009




Protection

Functions


Each protection stage can independently be enabled or disabled
according to the requirements of the intended application.

The device limits the maximum number of enabled stages to about
30, depending on the type of the stages. For more information,
please see the configuration instructions in Chapter 2 in the first part
of this manual.


Table 3.1 – List of Protection Functions

IEEE/

ANSI code

IEC Symbol

Function Name

50/51

3I>, 3I>>, 3I’>, 3I’>>

Overcurrent protection

87

∆I>, ∆I>>

Differential overcurrent protection

46 I

2

>, I’

2

> Current

unbalance

protection

49

T>

Thermal overload protection

50N/51N

I

0

>,

I

0

>>,

I

0

>>>,

I

0

>>>>

Earth fault protection

50BF

CBFP

Circuit-breaker failure protection

99 Prg1...8

Programmable

stages

50ARC

50NARC

ArcI>, ArcI’>
ArcI

01

>, ArcI

02

>

Optional arc fault protection


Setting

Groups


Most stages have two setting groups. Changing between setting
groups can be controlled manually or using any of the digital inputs,
virtual inputs, virtual outputs or LED indicator signals. By using
virtual I/O the active setting group can be controlled using the local
panel mimic display, any communication protocol or using the
inbuilt programmable logic functions.

Maximum Number of

Protection Stages

in one application

General Features of

Protection Stages

Protection Functions