Object states, Basic settings for controllable objects, Output signals of controllable objects – Rockwell Automation 865 Differential Protection Relay User Manual

Page 124

Advertising
background image



6-6 Control

Functions

865-UM001A-EN-P – July 2009

Object

States

Each object has the following states:

Table 6.6 – Object States

Setting

Value

Description

Undefined (00)

Open

Close

Object state

Undefined (11)

Actual state of the object

Basic Settings for Controllable Objects

Each controllable object has the following settings:

Table 6.7 – Basic Settings for Controllable Objects

Setting

Value

Description

DI for ‘obj open’

Open information

DI for ‘obj close’

Close information

DI for ‘obj ready’

None, any digital input,

virtual input or virtual output

Ready information

Max ctrl pulse length

0.02 … 600 s

Pulse length for open and close
commands

Completion timeout

0.02 … 600 s

Timeout of ready indication

Object control

Open/Close

Direct object control


If changing states takes longer than the time defined by “Max ctrl
pulse length” setting, object fails and “Object failure” matrix signal
is set. Also undefined-event is generated. “Completion timeout” is
only used for the ready indication. If “DI for ‘obj ready’” is not set,
completion timeout has no meaning.

Output signals of Controllable Objects

Each controllable object has 2 control signals in matrix:

Table 6.8 – Output Signals of Controllable Objects

Output signal

Description

Object x Open

Open control signal for the object

Object x Close

Close control signal for the object


These signals send control pulse when an object is controlled by
digital input, remote bus, auto-reclose etc.