Calculating the stabilizing resistance rs, Value of stabilizing resistor rs, Voltage limitation – Rockwell Automation 865 Differential Protection Relay User Manual

Page 145: Calculating the stabilizing resistance r, Vdr value and actual sensitivity

Advertising
background image



Applications

8-3

865-UM001A-EN-P – July 2009

Value of stabilizing resistor R

S

The

voltage

V

S

(Figure 8.1) is:

Equation

8.1

W

CT

PRIM

SEC

MAXT

S

R

R

CT

CT

I

V

+

=

I

MAXT

=

Maximum through fault current not to cause an REF trip

CT

SEC

=

Nominal secondary current of the CT

CT

PRI

=

Nominal primary current of the CT

R

CT

=

Resistance of CT secondary.

R

W

=

Total resistance of wiring, connections etc.


The CT should be of class X (see “CT Requirements” on page 8-2)
and the knee point voltage should be twice the calculated V

S

.

Selecting a low value helps to achieve more sensitivity and helps to avoid the usage of

a voltage limiting VDR. An unselective earth fault pick-up/trip is not always a problem if
a fast overcurrent stage will clear the fault anyway.

The stabilizing resistor R

S

is calculated as:

Equation

8.2

R

V

I

S

S

Set

=

I

Set

= Setting value of the relay as secondary value.

Voltage

Limitation

During heavy inside faults the voltage in the secondary circuit may
rise to several kilovolts depending on the fault currents, CT
properties and the stabilizing resistor R

S

. If the secondary voltage

would exceed 2 kV it should be limited using a voltage dependent
resistor (VDR).

The peak voltage according a linear CT model is:

Equation

8.3

S

W

CT

PRIM

SEC

MAXF

p

R

R

B

CT

CT

I

V

+

+

=

I

MAXF

= Maximum fault current when the fault is inside the

protected zone

CT

SEC

= Nominal secondary current of the CT

CT

PRI

= Nominal primary current of the CT

R

CT

= Resistance of CT secondary.

Calculating the Stabilizing
Resistance R

S

, VDR Value

and Actual Sensitivity

Advertising