Rms values, Demand values, Minimum and maximum values – Rockwell Automation 865 Differential Protection Relay User Manual

Page 113

Advertising
background image



Measurement Functions

5-3

865-UM001A-EN-P – July 2009

RMS Values

RMS

Currents

Relay calculates the RMS value of each phase current. The
minimum and the maximum of RMS values are recorded and
stored.

2

15

2

2

2

1

...

f

f

f

rms

I

I

I

I

+

+

+

=

Demand Values

The relay calculates average i.e. demand values of phase currents I

L1

,

I

L2

, I

L3

. The demand time is configurable from 10 minutes to 30

minutes with parameter "Demand time".

Table 5.5 – Demand Value Parameters

Parameter

Value

Unit

Description

Set

Time

10 ... 30

min

Demand time (averaging time)

Set

Fundamental frequency values

IL1da

A

Demand of phase current IL1

IL2da

A

Demand of phase current IL2

IL3da

A

Demand of phase current IL3

RMS values

IL1da

A

Demand of phase current IL1

IL2da

A

Demand of phase current IL2

IL3da

A

Demand of phase current IL3



Minimum and maximum values are registered with time stamps
since the latest manual clearing or since the device has been
restarted. The available registered min & max values are listed in the
following table.

Table 5.6 – Minimum and Maximum Values

Min & Max measurement

Description

IL1, IL2, IL3

Phase current (fundamental frequency value)

IL1RMS, IL2RMS, IL3RMS

Phase current, rms value

Io1, Io2

Residual current

f Frequency

IL1da, IL2da, IL3da

Demand values of phase currents

IL1da, IL2da, IL3da (rms value)

Demand values of phase currents, rms values

The clearing parameter "ClrMax" is common for all these values.

Table 5.7 – Parameters

Parameter

Value

Description

Set

ClrMax –

Clear

Reset all minimum and maximum
values

S

Minimum and Maximum
Values