7-12 Communications

865-UM001A-EN-P – July 2009



The device will accept:

ASDU 6: Time synchronization

ASDU 7: Initiation of general interrogation and

ASDU 20: General command


The data in a message frame is identified by:

type identification

function type and

information number


These are fixed for data items in the compatible range of the
protocol, for example, the trip of I> function is identified by: type
identification = 1, function type = 160 and information number = 90.
"Private range" function types are used for such data items, which
are not defined by the standard (e.g. the status of the digital inputs
and the control of the objects).

The function type and information number used in private range
messages is configurable. This enables flexible interfacing to
different master systems.

Table 7.9 – Parameters

Parameter

Value

Unit

Description

Note

Addr

1 – 254

An unique address within the system

Set

bit/s

9600
19200

bps

Communication speed

Set

MeasInt

200 – 10000

ms

Minimum measurement response
interval

Set

SyncRe

Sync
Sync+Proc
Msg
Msg+Proc

ASDU6 response time mode

Set

Set = An editable parameter (password needed)