Applications 8-17 – Rockwell Automation 865 Differential Protection Relay User Manual

Page 159

Advertising
background image



Applications

8-17

865-UM001A-EN-P – July 2009

CB

CLOSE COIL

OPEN COIL

-V

AUX

-V

AUX

Delay

Alarm relay

for trip

circuit failure

close control

trip circuit

failure alarm

R1

+V

AUX

865

Digital input

Trip relay

relay compartment

circuit breaker compartment

+

K1

1

DI

+48 V

A snap in relay module K1:

Phoenix Contact EMG 17-REL/KSR-120/21 Au

Coil: 96 .. 127 V, 24 kohm

Contact material: 5 mm Au (AgPd60)

Width: 17.5 mm

Assembly: DIN EN 50022 mounting rail

TripCircuitSup200OpenP os

Figure 8.11 – Typical Trip Circuit Supervision when Circuit-breaker is Open

(Supervised circuitry in this CB position is double-lined.)

Advertising