Ct requirement for protection – Rockwell Automation 865 Differential Protection Relay User Manual

Page 150

Advertising
background image



8-8 Applications

865-UM001A-EN-P – July 2009

CT Requirement for Protection

When the through current equals and exceeds k

A

xI

N

there may be

enough secondary differential current to trip a relay although there is
no in zone fault. This is because the CTs are unique and they do not
behave equally when approaching saturation.

To avoid false trips caused by heavy through faults the actual
accuracy limit factor k

A

of the CTs should exceed the relative setting

I

SET

of the non-stabilized differential stage.

Equation

8.8

NCT

NTra

SET

A

I

I

I

c

k

>

c =

Safety

factor

I

SET

=

Relative setting of the non-stabilized differential current
stage

I

NTra

=

Rated current of the transformer (primary side or
secondary side)

I

NCT

=

Rated primary current of the CT (primary side or
secondary side)


Using slightly smaller safety factor than indicated in Table 8.2 will
increase the setting inaccuracy.

Table 8.2 – Safety Factors

Protection Application

Safety Factor c

Overcurrent 2

Earth-fault, cable transformer

3

Earth-fault overcurrent, sum of three phase currents

6

Transformer differential, -winding or unearthed Y-winding

3

Transformer differential, earthed Y-winding

4

Generator differential

3

Sensitive earth-fault current settings, < 5% x In, should be avoided in this configuration

because a set of three CTs are not exactly similar and will produce some secondary
residual current, even though there is no residual current in the primary side.

Advertising