Rockwell Automation 865 Differential Protection Relay User Manual

Page 148

Advertising
background image



8-6 Applications

865-UM001A-EN-P – July 2009

Equation

8.5

%

100

)

(

1

2

0

=

P

T

P

S

N

C

I

dt

i

i

K

T

ε

T = Cycle

time

K

N

=

Rated transformation ratio I

NPrimary

/I

Nsecondary

i

S

=

Instantaneous secondary current

i

P

=

Instantaneous primary current

I

P

=

Rms value of primary current

NOTE: All current based protection functions of Allen-Bradley
relays, except arc protection, thermal protection and 2nd harmonic
blocking functions, are using the fundamental frequency component
of the measured current. The IEC formula includes an RMS value of
the current. That is why the composite error defined by IEC 60044-1
is not ideal for Allen-Bradley relays. However the difference is not
big enough to prevent rough estimation.

Standard accuracy classes

At rated frequency and with rated burden connected, the amplitude
error, phase error and composite error of a CT shall not exceed the
values given in the following table.

Table 8.1 – Values for Standard Accuracy Classes

Accuracy

class

Amplitude error at

rated primary

current

(%)

Phase displacement

at rated primary

current

(°)

Composite error

C

at

rated accuracy limit

primary current

(%)

5P

±1

±1

5

10P

±3

- 10


Marking:

The accuracy class of a CT is written after the rated power.

E.g. 10 VA 5P10, 15 VA 10P10, 30 VA 5P20

Accuracy Limit Current I

AL

Current transformers for protection must retain a reasonable
accuracy up to the largest relevant fault current. Rated accuracy
limit current is the value of primary current up to which the CT will
comply with the requirements for composite error ε

C

.

Advertising