Running hour counter, Timers – Rockwell Automation 865 Differential Protection Relay User Manual

Page 106

Advertising
background image



4-14 Supporting

Functions

865-UM001A-EN-P – July 2009

Running Hour Counter

This function calculates the total active time of the selected digital
input, virtual I/O or output matrix output signal. The resolution is
ten seconds.

Table 4.10 – Running Hour Counter Parameters

Parameter

Value

Unit

Description

Note

Runh

0 ... 876000

h

Total active time, hours
Note: The label text "Runh" can be
edited with SetPointPS.

(Set)

0 ... 3599

s

Total active time, seconds

(Set)

Starts

0 ... 65535

Activation counter

(Set)

Status Stop

Run

Current status of the selected digital
signal

DI


DI1 ...DI6,
VI1...VI4,
LedAl,
LedTr,
LedA,
LedB,
LedC,
LedDR
VO1...VO6

Select the supervised signal
None
Physical inputs
Virtual inputs
Output matrix out signal Al
Output matrix out signal Tr
Output matrix out signal LA
Output matrix out signal LB
Output matrix out signal LC
Output matrix out signal DR
Virtual outputs

Set

Started at

Date and time of the last activation

Stopped at

Date and time of the last inactivation

Set = An editable parameter (password needed)
(Set) = An informative value which can be edited as well.


Timers

The Allen-Bradley protection platform includes four settable timers
that can be used together with the user's programmable logic or to
control setting groups and other applications that require actions
based on calendar time. Each timer has its own settings. The selected
on-time and off-time is set and then the activation of the timer can be
set to be as daily or according the day of week (See the setting
parameters for details). The timer outputs are available for logic
functions and for the block and output matrix.