Recorded values of the latest eight faults – Rockwell Automation 865 Differential Protection Relay User Manual

Page 58

Advertising
background image

3-14 Protection

Functions

865-UM001A-EN-P – July 2009

Table 2.7 – Parameters of the Overcurrent Stages I>>, I’>> (50/51)

Parameter

Value

Unit

Description

Note

Status

-
Blocked
Start
Trip

Current status of the stage


F
F

SCntr

Cumulative start counter

C

TCntr

Cumulative

trip

counter

C

SetGrp

1 or 2

Active setting group

Set

SGrpDI


-
DIx
VIx
LEDx
VOx

Digital signal to select the active setting group
None
Digital input
Virtual input
LED indicator signal
Virtual output

Set

Force

Off
On

Force flag for status forcing for test
purposes. This is a common flag for all
stages and output relays, too. Automatically
reset by a 5-minute timeout.

Set

ILmax

A

The supervised value. Max. of IL1, IL2 and IL3

I>>, I>>>

A

Pick-up value scaled to primary value

I>>, I>>>

xIn

Pick-up setting

Set

t>>, t>>>

s

Definite operation time

Set

For details of setting ranges see “Protection Stages” in Chapter 10.

Set = An editable parameter (password needed)

C = Can be cleared to zero

F = Editable when force flag is on

Recorded Values of the Latest Eight Faults

Detailed information is available on the eight latest faults: Time
stamp, fault type, fault current, load current before the fault, elapsed
delay and setting group.

Table 2.8 – Recorded Values of the Overcurrent Stages (8 latest faults) I>, I>>, I>>> (50/51)

Parameter

Value

Unit

Description

yyyy-mm-dd

Time stamp of the recording, date

hh:mm:ss.ms

Time stamp, time of day

Type

1-N
2-N
3-N

1-2
2-3
3-1

1-2-3

Fault

type

Ground fault
Ground fault
Ground fault
Two phase fault
Two phase fault
Two phase fault
Three phase fault

Flt

xIgn

Maximum fault current

Load

xIgn

1 s average phase currents before the fault

EDly

%

Elapsed time of the operating time setting. 100% = trip

SetGrp 1

2

Active setting group during fault