Rockwell Automation 865 Differential Protection Relay User Manual

Page 52

Advertising
background image

3-8 Protection

Functions

865-UM001A-EN-P – July 2009


Table 3.2 – Zero Current Compensation in Transformer Applications

Relay setting

Transformator

Connection group

ConnGrp

Io cmps

I'o cmps

YNy0 Yy0

ON

OFF

YNyn0 Yy0

ON

ON

Yy0 Yy0

OFF

OFF

Yyn0 Yy0

OFF

ON

YNy6 Yy6

ON

OFF

YNyn6 Yy6

ON

ON

Yy6 Yy6

OFF

OFF

Yyn6 Yy6

OFF

ON

Yd1 Yd1

OFF

OFF

YNd1 Yd1

ON

OFF

Yd5 Yd5

OFF

OFF

YNd5 Yd5

ON

OFF

Yd7 Yd7

OFF

OFF

YNd7 Yd7

ON

OFF

Yd11 Yd11

OFF

OFF

YNd11 Yd11

ON

OFF

Dy1 Dy1

OFF

OFF

Dyn1 Dy1

OFF

ON

Dy5 Dy5

OFF

OFF

Dyn5 Dy5

OFF

ON

Dy7 Dy7

OFF

OFF

Dyn7 Dy7

OFF

ON

Dy11 Dy11

OFF

OFF

Dyn11 Dy11

OFF

ON


Table 3.3 – Zero Current Compensation in Generator Applications

Relay setting

Genarator only

ConnGrp

Io cmps

I'o cmps

None earthing

Yy0

OFF

OFF