Rockwell Automation 865 Differential Protection Relay User Manual

Page 102

Advertising
background image



4-10 Supporting

Functions

865-UM001A-EN-P – July 2009


Equation

4.4

C

C

AlarmMax

=

Δ

3

313

945

2

1

=

=

Δ

=

Δ

L

L


Thus Alarm2 counters for phases L1 and L2 are decremented by 3.
In phase L1 the currents is less than the alarm limit current 6 kA. For
such currents the decrement is one.

1

3

=

Δ

L

Table 4.8 – Local Panel Parameters of CBWEAR Function

Parameter

Value

Unit

Description

Set

CBWEAR STATUS

Al1L1
Al1L2
Al1L3
Al2L1
Al2L2
Al2L3


Operations left for
- Alarm 1, phase L1
- Alarm 1, phase L2
- Alarm 1, phase L3
- Alarm 2, phase L1
- Alarm 2, phase L2
- Alarm 2, phase L3

Latest trip
Date
time

Time stamp of the latest trip
operation

IL1
IL2
IL3

A

A
A

Broken current of phase L1
Broken current of phase L2
Broken current of phase L3

CBWEAR SET
Alarm1

Current

0.00 – 100.00

kA

Alarm1 current level

Set

Cycles

100000 – 1

Alarm1 limit for operations left

Set

Alarm2

Current

0.00 – 100.00

kA

Alarm2 current level

Set

Cycles

100000 – 1

Alarm2 limit for operations left

Set

CBWEAR SET2
Al1On On

Off

'Alarm1 on' event enabling

Set

Al1Off On

Off

'Alarm1 off' event enabling

Set

Al2On On

Off

'Alarm2 on' event enabling

Set

Al2Off On

Off

'Alarm2 off' event enabling

Set

Clear –

Clear

Clearing of cycle counters

Set

Set = An editable parameter (password needed)
The breaker curve table is edited with SetPointPS.