Applications

8-7

865-UM001A-EN-P – July 2009

Accuracy limit factor k

ALF

The ratio of the accuracy limit current to the rated primary current.

Equation

8.6

N

AL

ALF

I

I

K

=


The standard accuracy limit factors are 5, 10, 15, 20 and 30.


Marking:

Accuracy limit factor is written after the accuracy class.

E.g. 10 VA 5P10, 15 VA 10P10, 30 VA 5P20.


The actual accuracy limit factor k

A

depends on the actual burden.

Equation

8.7

A

i

N

i

ALF

A

S

S

S

S

k

k

+

+

=

k

ALF

=

Accuracy limit factor at rated current and rated burden

S

i

=

Internal secondary burden. (Winding resistance R

CT

in

Figure 8.3)

S

N

=

Rated burden

S

A

=

Actual burden including wiring and the load.

Figure 8.4 – Effect of CT Winding Resistance

This figure of Equation 8.7 shows that it is essential to know the
winding resistance R

CT

of the CT if the load is much less than the

nominal. A 10 VA 5P10 CT with 25% load gives actual ALF values
from 15..30 when the winding resistance varies from 0.5 Ω to 0.05 Ω.