Circuit-breaker failure protection, Arc fault protection stages (option) – Rockwell Automation 865 Differential Protection Relay User Manual

Page 179

Advertising
background image



Technical Data

10-9

865-UM001A-EN-P – July 2009

Circuit-breaker Failure Protection

Table 10.23 – Circuit-breaker failure protection CBFP (50BF)

Relay to be supervised

T1-T12

Definite time function

- Operating time

0.1 – 10.0 s (step 0.1 s)

Reset time

<95 ms

Inaccuracy
- Operating time

±20 ms

This is the instantaneous time i.e. the minimum total operational time including the fault

detection time and operation time of the trip contacts.

Arc Fault Protection Stages (Option)

The operation of the arc protection depends on the setting value of the
ArcI>, ArcI

0

> and ArcI

02

> current limits. The arc current limits cannot be

set, unless the relay is provided with the optional arc protection card.

Table 10.24 – Arc Protection Stage ArcI> (50AR), Option

Setting range

0.5 - 10.0 x I

n

Arc sensor connection

S1, S2, S1/S2, BI, S1/BI, S2/BI, S1/S2/BI

- Operating time (Light only)

13 ms

- Operating time (4xIset + light)

17ms

- Operating time (BIN)

10 ms

- BO operating time

<3 ms

Reset time

<95 ms

Reset time (Delayed ARC L)

<120 ms

Reset time (BO)

<80 ms

Reset ratio

0.90

Inaccuracy:
- Starting

10% of the set value

- Operating time

±5 ms

- Delayed ARC light

±10 ms

Table 10.25 –Arc protection stage ArcI

0

> (50AR), option

Setting range

0.5 - 10.0 x I

n

Arc sensor connection

S1, S2, S1/S2, BI, S1/BI, S2/BI, S1/S2/BI

- Operating time (Light only)

13 ms

- Operating time (4xIset + light)

17ms

- Operating time (BIN)

10 ms

- BO operating time

<3 ms

Reset time

<95 ms

Reset time (Delayed ARC L)

<120 ms

Reset time (BO)

<80 ms

Reset ratio

0.90