Rockwell Automation 865 Differential Protection Relay User Manual

Page 57

Advertising
background image



Protection Functions

3-13

865-UM001A-EN-P – July 2009

Table 2.6 – Parameters of the Overcurrent Stage I> and I’> (50/51)

Parameter

Value

Unit

Description

Note

Status -

Blocked
Start
Trip

Current status of the stage


F
F

TripTime

s

Estimated time to trip

SCntr

Cumulative start counter

Clr

TCntr

Cumulative

trip

counter

Clr

SetGrp

1 or 2

Active setting group

Set

SGrpDI


-
DIx
VIx
LEDx
VOx

Digital signal to select the active setting
group
None
Digital input
Virtual input
LED indicator signal
Virtual output



Set

Force Off

On

Force flag for status forcing for test
purposes. This is a common flag for all
stages and output relays, too. This flag is
automatically reset 5 minutes after the last
front panel push button pressing.

Set

ILmax

A

The supervised value. Max. of IL1, IL2
and IL3

I>

A

Pick-up value scaled to primary value

I>

xIgn

Pick-up

setting

Set

Curve

DT
IEC
IEEE
IEEE2
RI
PrgN

Delay curve family:
Definite time
Inverse time. See “Inverse Time
Operation”.

Pre 1996



Set

Type

DT
NI
VI
EI
LTI
Parameters

Delay type.
Definite time
Inverse time. See “Inverse Time
Operation”.



Set

t>

s

Definite operation time (for definite time
only)

Set

k>

Inverse delay multiplier (for inverse time
only)

Set

Dly20x

s

Delay

at

20xIset

Dly4x

s

Delay

at

4xIset

Dly2x

s

Delay

at

2xIset

Dly1x

s

Delay

at

1xIset

A, B, C, D,
E

User's constants for standard equations.
Type=Parameters. See “Inverse Time
Operation”.

Set

For details of setting ranges see “Protection Stages” in Chapter 10.

Set = An editable parameter (password needed)

C = Can be cleared to zero

F = Editable when force flag is on