Setting alarm points – Rockwell Automation 865 Differential Protection Relay User Manual

Page 99

Advertising
background image



Supporting Functions

4-7

865-UM001A-EN-P – July 2009



The points 4...8 are not needed for the CB in Figure 4.1. Thus
they are set to 100 kA and one operation in the table to be
discarded by the algorithm.

10

20

50

100

1000

10000

100000

100

200

500 1000

10000

100000

Number

of

permitted

operations

Breaked current (A)

CBWEARcharacteristics

Figure 4.1 – An example of circuit breaker wearing characteristic graph

Table 4.7 – Example of Circuit Breaker Wearing Characteristics

Point

Interrupted current (kA)

Number of permitted operations

1

0 (mechanical age)

10000

2

1.25 (rated current)

10000

3

31.0 (maximum breaking current)

80

4 100

1

5 100

1

6 100

1

7 100

1

8 100

1

Note: Values taken from Figure 4.1. The table is edited with SetPointPS under menu

“Breaker Curve”.

Setting Alarm Points

There are two alarm points available having two setting parameters
each.

Current

The first alarm can be set for example to nominal current of the
CB or any application typical current. The second alarm can be
set for example according a typical fault current.

Operations left alarm limit
An alarm is activated when there are less operation left at the
given current level than this limit.

Advertising