Connections

9-7

865-UM001A-EN-P – July 2009



X4 Rear Panel Connector (Local RS232 and Extension RS485 ports)

Table 9.3 – Rear Panel Connector Signals

Rear panel port (LOCAL)

Pin

Signal

X4 1

No

connection

X4

2

Rx in, RS232 local

X4

3

Tx out, RS232 local

X4

4

DTR out (+8 V)

X4 5

GND

X4 6

No

connection

X4

7

B RS485 extension port

X4

8

A+ RS485 extension port

X4 9

No

connection

NOTE: In the Allen-Bradley relays, a positive RS485 voltage from

A+ to B corresponds to bit value “1”. In the X4 connector
the RS485 extension port is not galvanically isolated.

1 2
3
4

Figure 9.7 – Dip Switches in RS-485 and Optic Fiber Options

Table 9.4 – DIP Switch Functions

Dip switch

number

Switch Position

Function

RS-485

Function

Fibre optics

1

Left

2-wire connection

Echo off

1

Right

4-wire connection

Echo on

2

Left

2-wire connection

Light on in idle state

2

Right

4-wire connection

Light off in idle state

3

Left

Termination On

Not applicable

3

Right

Termination Off

Not applicable

4

Left

Termination On

Not applicable

4

Right

Termination Off

Not applicable

NOTE: The internal 2-wire RS485 port in X4 connector is not

galvanically isolated.