5-6 Measurement

Functions

865-UM001A-EN-P – July 2009

Example

1: Secondary to per unit and percent for phase currents

excluding ArcI>.
CT

PRI

= 150/1

CT

SEC

= 800/5

S

N

= 25 MVA

U

N

= 110 kV

U'

N

= 21 kV


Current injected to the relay's primary side input is 175 mA and 859
mA for the secondary side input.

The rated current on HV and LV side will be
I

N

= 25 MVA/ (

√3 x 110 kV) = 131.2 A

I'

N

= 25 MVA/ (

√3 x 21 kV) = 687.3 A


⇒ Per unit currents are
I

PU

= 0.175x150/(1x131.2) = 0.20 pu = 20 %xI

N

(HV side)

I'

PU

= 0.859x800/(5x687.3) = 0.20 pu = 20 % (LV side)

Example 2: Secondary to per unit for ArcI>.
CT = 750/5
Current injected to the relay's inputs is 7 A.
⇒ Per unit current is
I

PU

= 7/5 = 1.4 pu = 140 %

Example

3: Per unit and percent to secondary for phase currents

excluding ArcI>.
CT

PRI

= 150/1

CT

SEC

= 800/5

S

N

= 25 MVA

U

N

= 110 kV

U'

N

= 21 kV

The relay setting is 0.20 pu = 20 %xI

N

.

The rated current on HV and LV side will be same as in example 1.
⇒ The corresponding secondary currents are
I

SEC

= 0.20xI

N

= 0.20x131.2x1/150 = 175 mA (HV side)

I'

SEC

= 0.20xI'

N

= 0.20x687.3x5/800 = 859 mA (LV side)

Example 4: Per unit to secondary for ArcI>.
CT = 750/5
The relay setting is 2 pu = 200 %.
⇒ Secondary current is
I

SEC

= 2x5 = 10 A

Example 5: Secondary to per unit for residual current.
Input is I

01

or I

02

.

CT

0

= 50/1

Current injected to the relay's input is 30 mA.
⇒ Per unit current is
I

PU

= 0.03/1 = 0.03 pu = 3 %