Rockwell Automation 865 Differential Protection Relay User Manual

Page 177

Advertising
background image



Technical Data

10-7

865-UM001A-EN-P – July 2009

Table 10.19 –Thermal overload stage T> (49)

Setting range:

0.1 – 2.40 x I

mot

or I

N

(step 0.01)

Alarm setting range:

60 – 99 % (step 1%)

Time constant Tau:

2 – 180 min (step 1)

Cooling time coefficient:

1.0 – 10.0 xTau (step 0.1)

Max. overload at +40 °C

70 – 120 %I

mot

(step 1)

Max. overload at +70 °C

50 – 100 %I

mot

(step 1)

Ambient temperature

-55 – 125 °C (step 1°)

Resetting ratio (Start & trip)

0.95

Accuracy:
- operating time

±5% or ±1 s

Table 10.20 – Unbalance stage I

2

>, I’

2

> (46)

Setting range:

2 – 70% (step 1%)

Definite time characteristic:

- operating time

1.0 – 600.0s s (step 0.1)

Inverse time characteristic:
- 1 characteristic curve
- time multiplier K

1

- Upper limit for inverse time


Inv
1 – 50 s (step 1)
1 000 s

Start time

Typically 300 ms

Reset time

<450 ms

Reset ratio

0.95

Inaccuracy:
- Starting
- Operate time


±3% of the set value or 0.5% of the rated value
±5% or ±150 ms