Rockwell Automation 865 Differential Protection Relay User Manual

Page 65

Advertising
background image



Protection Functions

3-21

865-UM001A-EN-P – July 2009

Table 3.12 – Parameters of the Undirectional Earth Fault Stage I

0

>>, I

0

>>>,

I

0

>>>> (50N/51N)

Parameter

Value

Unit

Description

Note

Status -

Blocked
Start
Trip

Current status of the stage


F
F

TripTime

s

Estimated time to trip

SCntr

Cumulative start counter

Clr

TCntr

Cumulative

trip

counter

Clr

SetGrp

1 or 2

Active setting group

Set

SGrpDI


-
DIx
VIx
LEDx
VOx

Digital signal to select the active setting
group
None
Digital input
Virtual input
LED indicator signal
Virtual output



Set

Force Off

On

Force flag for status forcing for test
purposes. This is a common flag for all
stages and output relays, too.
Automatically reset by a 5-minute
timeout.

Set

Io
Io2
IoCalc

pu

The supervised value according the
parameter "Input" below.

Io>>
Io>>>
Io>>>>

A

Pick-up value scaled to primary value

Io>>
Io>>>
Io>>>>

pu

Pick-up setting relative to the parameter
"Input" and the corresponding CT value

Set

t>

s

Definite operation time (for definite time
only)

Set

Input Io1

Io2
IoCalc
I’oCalc

X1-7&8. See Chapter 4.
X1-9&10
IL1 + IL2 + IL3
I’L1 + I’L2 + I’L3


Set

For details of setting ranges see “Protection Stages” in Chapter 10.

Set = An editable parameter (password needed)

C = Can be cleared to zero

F = Editable when force flag is on