System clock parameters – Rockwell Automation 865 Differential Protection Relay User Manual

Page 105

Advertising
background image



Supporting Functions

4-13

865-UM001A-EN-P – July 2009

Table 4.9 – System Clock Parameters

Parameter

Value

Unit

Description

Note

Date

Current

date

Set

Time

Current

time

Set

Style

Y–d–m
d.m.y
m/d/y

Date

format

Year-Month-Day
Day.Month.Year
Month/Day/Year

Set

SyncDI



DI1 ... DI6

The digital input used for clock
synchronisation.
DI not used for synchronizing
Minute pulse input

TZone –12.00

...

+14.00

UTC time zone for SNTP synchronization.
Note: This is a decimal number. For example
for state of Nepal the time zone 5:45 is given
as 5.75

Set

DST No

Yes

Daylight saving time for SNTP

Set

SySrc

Internal
DI
SNTP
SpaBus
ModBus
ProfibusDP
IEC-103
DNP3

Clock synchronisation source
No sync recognized since 200 s
Digital input
Protocol sync
Protocol sync
Protocol sync
Protocol sync
Protocol sync
Protocol sync

MsgCnt

0 ... 65535, 0 ...
etc.

The number of received synchronisation
messages or pulses

Dev

±32767

ms

Latest time deviation between the system
clock and the received synchronization

SyOS

±10000.000

s

Synchronisation correction for any constant
error in the synchronizing source.
A positive value will compensate a lagging
external sync and communication delays. A
negative value will compensate any leading
offset of the external synch source.

Set

AAIntv

±10000

s

Adapted auto adjust interval for 1 ms
correction

Set

AvDrft Lead

Lag

Adapted average clock drift sign

Set

FilDev

±125

ms Filtered

synchronisation

deviation

Set = An editable parameter (password needed)

Astronomically a range –11 ... +12 h would be enough, but for political and geographical reasons a
larger range is needed.

If external synchronization is used this parameter will be set automatically.

Set the DI delay to its minimum and the polarity such that the leading edge is the synchronizing
edge.

System Clock
Parameters