Casing, Package, Protection stages – Rockwell Automation 865 Differential Protection Relay User Manual

Page 175: Differential protection

Advertising
background image



Technical Data

10-5

865-UM001A-EN-P – July 2009


Table 10.13 – Casing

Degree of protection (IEC 60529)

IP20

Dimensions (W x H x D)

208 x 155 x 225 mm

Material

1 mm steel plate

Weight

4.2 kg

Colour code

RAL 7032 (Casing) / RAL 7035 (Back plate)

Table 10.14 – Package

Dimensions (W x H x D)

215 x 160 x 275 mm

Weight (Terminal, Package and Manual)

5.2 kg

Protection Stages

Differential Protection

Table 10.15 – Differential overcurrent stage ΔI> (87)

Setting range

5 - 50 % I

n

Bias current for start of slope 1

0.50 x I

n

Slope 1

5 - 100 %

Bias current for start of slope 2

1.00 - 3.00 x I

n

Slope 2

100 - 200 %

Second harmonic blocking

5 - 30 %, or disable

Reset time

< 60 ms

Reset ratio

0.95

Inaccuracy:
- Starting

±3% of set value or ±0.5% of rated value

- Operating time (I

d

> 1.2 x I

set

) <

60

ms

- Operating time (I

d

> 3 x I

set

)

<

50

ms


Table 10.16 – Differential overcurrent stage ΔI>> (87)

Setting range

5.0 - 40.0 x I

n

Reset time

< 60 ms

Reset ratio

0.95

Inaccuracy:
- Starting

±3% of set value or ±0.5% of rated value

- Operating time

< 40 ms

Advertising