Dnp 3.0 – Rockwell Automation 865 Differential Protection Relay User Manual
Page 139

Communications
7-13
865-UM001A-EN-P – July 2009
Table 7.10 – Parameters for Disturbance Record Reading
Parameter
Value
Unit
Description
Note
ASDU23 On
Off
Enable record info message
Set
Smpls/msg
1–25
Record samples in one message
Set
Timeout
10–10000
s
Record reading timeout
Set
Fault
Fault identifier number for IEC-103.
Starts + trips of all stages.
TagPos
Position of read pointer
Chn
Active
channel
ChnPos
Channel read position
Fault numbering
Faults
Total number of faults
GridFlts
Fault burst identifier number
Grid
Time window to classify faults
together to the same burst.
Set
Set = An editable parameter (password needed)
DNP
3.0
The relay supports communication using DNP 3.0 protocol.
The following DNP 3.0 data types are supported:
•
binary input
•
binary input change
•
double-bit input
•
binary output
•
analog input
•
counters
DNP 3.0 communication is activated via menu selection. RS-485
interface is often used but also RS-232 and fiber optic interfaces are
possible.