Dnp 3.0 – Rockwell Automation 865 Differential Protection Relay User Manual

Page 139

Advertising
background image



Communications

7-13

865-UM001A-EN-P – July 2009

Table 7.10 – Parameters for Disturbance Record Reading

Parameter

Value

Unit

Description

Note

ASDU23 On

Off

Enable record info message

Set

Smpls/msg

1–25

Record samples in one message

Set

Timeout

10–10000

s

Record reading timeout

Set

Fault

Fault identifier number for IEC-103.
Starts + trips of all stages.

TagPos

Position of read pointer

Chn

Active

channel

ChnPos

Channel read position

Fault numbering
Faults

Total number of faults

GridFlts

Fault burst identifier number

Grid

Time window to classify faults
together to the same burst.

Set

Set = An editable parameter (password needed)

DNP

3.0

The relay supports communication using DNP 3.0 protocol.

The following DNP 3.0 data types are supported:

binary input

binary input change

double-bit input

binary output

analog input

counters

DNP 3.0 communication is activated via menu selection. RS-485
interface is often used but also RS-232 and fiber optic interfaces are
possible.