3-42 Protection

Functions

865-UM001A-EN-P – July 2009

Example for Delay type "Moderately inverse (MI)":

k = 0.50
I

=

4 pu

I

pickup

=

2 pu

A = 0.1735
B = 0.6791
C = 0.8
D = -0.08
E = 0.127

38

.

0

8

.

0

2

4

127

.

0

8

.

0

2

4

08

.

0

8

.

0

2

4

6791

.

0

1735

.

0

5

.

0

3

2

=

⎛ −

+

⎛ −

+

⎛ −

+

=

t


The operation time in this example will be 0.38 seconds. The same result
can be read from Figure 3.26.


Figure 3.26 – IEEE2 Moderately

Figure 3.27 – IEEE2 Normal

Inverse Delay

Inverse Delay