3-42 Protection
Functions
865-UM001A-EN-P – July 2009
Example for Delay type "Moderately inverse (MI)":
k = 0.50
I
=
4 pu
I
pickup
=
2 pu
A = 0.1735
B = 0.6791
C = 0.8
D = -0.08
E = 0.127
38
.
0
8
.
0
2
4
127
.
0
8
.
0
2
4
08
.
0
8
.
0
2
4
6791
.
0
1735
.
0
5
.
0
3
2
=
⎥
⎥
⎥
⎥
⎦
⎤
⎢
⎢
⎢
⎢
⎣
⎡
⎟
⎠
⎞
⎜
⎝
⎛ −
+
⎟
⎠
⎞
⎜
⎝
⎛ −
−
+
⎟
⎠
⎞
⎜
⎝
⎛ −
+
⋅
=
t
The operation time in this example will be 0.38 seconds. The same result
can be read from Figure 3.26.