Rockwell Automation 865 Differential Protection Relay User Manual

Page 83

Advertising
background image



Protection Functions

3-39

865-UM001A-EN-P – July 2009

Table 3.24 – Constants for IEEE/ASI Inverse Delay Equation

Parameter

Delay type

A

B

C

LTI Long

time

inverse

0.086

0.185

0.02

LTVI

Long time very inverse

28.55

0.712

2

LTEI

Long time extremely inverse

64.07

0.250

2

MI Moderately

inverse

0.0515

0.1140

0.02

VI Very

inverse

19.61

0.491

2

EI Extremely

inverse

28.2

0.1217

2

STI

Short time inverse

0.16758

0.11858

0.02

STEI

Short time extremely inverse

1.281

0.005

2

Example for Delay type "Moderately inverse (MI)":

k =

0.50

I =

4

pu

I

pickup

=

2

pu

A =

0.0515

B =

0.114

C =

0.02

9

.

1

1140

.

0

1

2

4

0515

.

0

50

.

0

02

.

0

=

+

=

t

The operation time in this example will be 1.9 seconds. The same result
can be read from Figure 3.23.

Figure 3.20 – ANSI/IEEE Long Time

Figure 3.21 – ANSI/IEEE Long Time

Inverse Delay

Very Inverse Delay

Advertising