Communications

7-11

865-UM001A-EN-P – July 2009

Table 7.8 – SPA-bus Parameters

Parameter

Value

Unit

Description

Note

Addr

1 – 899

SPA-bus address. Must be unique in
the system.

Set

bit/s

1200
2400
4800
9600
(default)
19200

bps

Communication speed

Set

Emode

Channel
(Limit60)
(NoLimit)

Event

numbering

style.

Use this for new installations.
(The other modes are for
compatibility with old systems.)

(Set)

Set = An editable parameter (password needed)

IEC

60870-5-103

The IEC standard 60870-5-103 "Companion standard for the
informative interface of protection equipment" provides standardized
communication interface to a primary system (master system).

The unbalanced transmission mode of the protocol is used, and the
device functions as a secondary station (slave) in the communication.
Data is transferred to the primary system using "data acquisition by
polling"-principle. The IEC functionality includes the following
application functions:

station initialization

general interrogation

clock synchronization and

command transmission


It is not possible to transfer parameter data or disturbance recordings
via the IEC 103 protocol interface.


The following ASDU (Application Service Data Unit) types will be
used in communication from the device:

ASDU 1: time tagged message

ASDU 3: Measurands I

ASDU 5: Identification message

ASDU 6: Time synchronization and

ASDU 8: Termination of general interrogation