Opening access, Password handling – Rockwell Automation 865 Differential Protection Relay User Manual

Page 27

Advertising
background image



Local Panel User Interface

2-15

865-UM001A-EN-P – July 2009

Opening

Access

1. Push the INFO key and the ENTER key on the front panel.

ENTER PASSWORD

0

***

Figure 2.15 – Opening the Access Level

2.

Enter the password needed for the desired level: the password

can contain four digits. The digits are supplied one by one by
first moving to the position of the digit using the RIGHT key and
then setting the desired digit value using the UP key.

3.

Push the ENTER key.

Password

Handling


The passwords can only be changed using SetPointPS software
connected to the local RS-232 port on the relay.


It is possible to restore the password(s) in case the password is lost or
forgotten. In order to restore the password(s), a relay program is
needed. The serial port settings are 38400 bps, 8 data bits, no parity
and one stop bit. The bit rate is configurable via the front panel.

Command

Description

get pwd_break

Get the break code (Example: 6569403)

get serno

Get the serial number of the relay (Example: 12345)

Send both the numbers to Rockwell Automation and ask for a
password break. A device specific break code is sent back to you.
That code will be valid for the next two weeks only for this specific
device.

Command

Description

set pwd_break=4435876

Restore the factory default passwords (“4435876” is
just an example. The actual code should be
requested from Rockwell Automation.)

Now the passwords are restored to the default values (See section
“Operating Levels”).