Rockwell Automation 865 Differential Protection Relay User Manual

Page 60

Advertising
background image

3-16 Protection

Functions

865-UM001A-EN-P – July 2009

0

1

10

100

1000

2

20

200

2000

5

50

500

20

Negative sequence current I (%)

2

CurrentUnbalanceChar

Operation

time

(s)

40

60

80

100

K = 1 s

1

K = 50 s

1

K = 2 %

2

K = 2 %

2

K = 40 %

2

K = 40 %

2

K = 70 %

2

K = 70 %

2


Figure 3.11 – Inverse operation delay of current unbalance stage I

2

>

The longest delay is limited to 1000 seconds (=16min 40s).

Table 3.9 – Parameters of the Current Unbalance Stage I

2

>, I’

2

> (46)

Parameter

Value

Unit

Description

Note

Status -

Blocked
Start
Trip

Current status of the stage


F
F

SCntr

Cumulative start counter

C

TCntr

Cumulative

trip

counter

C

SetGrp

1 or 2

Active setting group

Set

SGrpDI


-
DIx
VIx
LEDx
VOx

Digital signal to select the active setting
group
None
Digital input
Virtual input
LED indicator signal
Virtual output

Set

Force Off

On

Force flag for status forcing for test
purposes. This is a common flag for all
stages and output relays, too.
Automatically reset by a 5-minute
timeout.

Set

I2/In

%In

The supervised value.

I2>

%In

Pick-up

setting

Set

t>

s

Definite operation time (Type=DT)

Set

Type DT

INV

Definite

time

Inverse time (Equation)

Set

K1

s

Delay multiplier (Type =INV)

Set

For details of setting ranges see “Protection Stages” in Chapter 10.

Set = An editable parameter (password needed)

C = Can be cleared to zero

F = Editable when force flag is on