Output matrix, Figure 6.1 – output matrix – Rockwell Automation 865 Differential Protection Relay User Manual

Page 122

Advertising
background image



6-4 Control

Functions

865-UM001A-EN-P – July 2009

Output Matrix

By means of the output matrix, the output signals of the various
protection stages, digital inputs, logic outputs and other internal
signals can be connected to the output relays, front panel indicators,
virtual outputs etc.

There are two LED indicators named "Alarm" and "Trip" on the
front panel. Furthermore there are three general purpose LED
indicators – "A", "B" and "C"  available for customer-specific
indications. In addition, the triggering of the disturbance recorder
(DR) and virtual outputs are configurable in the output matrix. See
an example in Figure 6.1.

An output relay or indicator LED can be configured as latched or
non-latched. A non-latched relay follows the controlling signal. A
latched relay remains activated although the controlling signal
releases.

There is a common "release latched" signal to release all the latched
relays. This release signal resets all the latched output relays and
indicators. The reset signal can be given via a digital input, via a
keypad or through communication. Any digital input can be used for
resetting. The selection of the input is done with the SetPointPS
software under the menu "Release output matrix latches". Under the
same menu, the "Release latches" parameter can be used for
resetting.

OUTPUT MATRIX

connected

I> start

I>> start

Io> start

Io>> start

I> trip

I>> trip

Io> trip

Io>> trip

T1

T2

A1

A2

A3

A4

A5

Alarm Trip

A

B

C

DR

VO1

connected and latched

OutputMatrix

Figure 6.1 – Output Matrix

Advertising