Iec inverse time operation – Rockwell Automation 865 Differential Protection Relay User Manual

Page 80

Advertising
background image



3-36 Protection

Functions

865-UM001A-EN-P – July 2009


Table 3.22 – Available Standard Delay Families and Types

Curve family

Delay type

DT

IEC

IEEE

IEEE2

RI

DT

Definite time

X

NI1

Normal

inverse

X X

VI

Very inverse

X

X

X

EI

Extremely inverse

X

X

X

LTI

Long

time

inverse

X X

LTEI

Long time extremely inverse

X

LTVI

Long time very inverse

X

MI

Moderately inverse

X

X

STI

Short time inverse

X

STEI

Short time extremely inverse

X

RI

Old ASEA type

X

RXIDG

Old ASEA type

X

IEC Inverse Time Operation

The operation time depends on the measured value and other
parameters according Equation 6. Actually this equation can only be
used to draw graphs or when the measured value I is constant during
the fault. A modified version is implemented in the relay for real
time usage.

Equation 6

1



=

B

pickup

I

I

A

k

t

t

=

Operation delay in seconds

k =

User’s

multiplier

I =

Measured

value

I

pickup

=

User’s pick up setting

A, B

=

Constants parameters according Table 3.23.


There are three different delay types according IEC 60255-3, Normal
inverse (NI), Extremely inverse (EI), Very inverse (VI) and a VI
extension, Long time inverse (LTI).