Optional two-channel arc protection card, Optional digital i/o card, Optional digital i/o card (di19/di20) – Rockwell Automation 865 Differential Protection Relay User Manual

Page 168

Advertising
background image

9-8 Connections

865-UM001A-EN-P – July 2009

NOTE: When this option card is installed, the parameter "Arc card

type" has value "2Arc+BI/O".

NOTE: If the slot X6 is already occupied with the DI19/DI20

digital input card, this option is not available, but there is
still one arc sensor channel available. (See ‘Optional
Digital I/O Card – DI19/DI20’ below.)


The optional arc protection card includes two arc sensor channels.
The arc sensors are connected to terminals X6: 4-5 and 6-7.

The arc information can be transmitted and/or received through
digital input and output channels. This is a 48 V dc signal.

Connections:

X6: 1

Binary input (BI)

X6: 2

Binary output (BO)

X6: 3

Common for BI and BO.

X6: 4-5

Sensor 1

X6: 6-7

Sensor 2

The binary output of the arc option card may be activated by the
arc sensors or by any available signal in the output matrix. The
binary output can be connected to an arc binary input of another
Allen-Bradley protection relay or manager.

NOTE: When this option card is installed, the parameter "Arc card

type" has value "Arc+2DI". With DI19/DI20 option only
one arc sensor channel is available.

NOTE: If the slot X6 is already occupied with the two-channel arc

sensor card, this option is not available.

The DI19/DI20 option enables two more digital inputs. These
inputs are useful in applications where the contact signals are not
potential free. For example trip circuit supervision is such
application. The inputs are connected to terminals X6:1 – X6:2
and X6:3 – X6:4.

Connections:

1 DI19+
X6:2 DI19-
X6:3 DI20+
X6:4 DI20-
X6:5 NC
X6:6 L+
X6:7 L-


Optional Two-Channel