Operating measures, Control functions – Rockwell Automation 865 Differential Protection Relay User Manual

Page 28

Advertising
background image



2-16

Local Panel User Interface

865-UM001A-EN-P – July 2009

Operating Measures

Control Functions


The default display of the local panel is a single-line diagram
including relay identification, Local/Remote indication, Auto-reclose
on/off selection and selected analogue measurement values.


Please note that the operator password must be active in order to be
able to control the objects. Please refer to ‘Opening Access’ on
page 2-15.

Toggling

Local/Remote

Control

1. Push the ENTER key. The previously activated object starts to

blink.

2. Select the Local/Remote object (“L” or “R” squared) by using

the arrow keys.

3. Push the ENTER key. The L/R dialog opens. Select “REMOTE”

to enable remote control and disable local control. Select
“LOCAL” to enable local control and disable remote control.

4. Confirm the setting by pushing the ENTER key. The

Local/Remote state will change.


Object

Control

1. Push the ENTER key. The previously activated object starts to

blink.

2. Select the object to control by using the arrow keys. Please note

that only controllable objects can be selected.

3. Push the ENTER key. A control dialog opens.

4. Select the “Open” or “Close” command by using the UP and

DOWN arrow keys.

5. Confirm the operation by pushing the ENTER key. The state of

the object changes.


Toggling Virtual Inputs

1. Push the ENTER key. The previously activated object starts to

blink.

2. Select the virtual input object (empty or black square)

3. The dialog opens

4. Select “VIon” to activate the virtual input or select “VIoff” to

deactivate the virtual input