Operating

Levels


The relay has three operating levels: User level, Operator level
and Configurator level. The purpose of the access levels is to
prevent accidental change of relay configurations, parameters or
settings.


USER

level

Use:

Possible to read e.g. parameter values,
measurements and events

Opening:

Level permanently open

Closing:

Closing not possible



OPERATOR

level

Use:

Possible to control objects and to change e.g. the
settings of the protection stages

Opening:

Default password is 1

Setting State:

Push ENTER

Closing:

The level is automatically closed after 10 minutes
idle time. Giving the password 9999 can also close
the level.



CONFIGURATION

level

Use:

The configurator level is needed during the
commissioning of the relay. E.g. the scaling of the
voltage and current transformers can be set.

Opening:

Default password is 0002

Setting State:

Push ENTER

Closing:

The level is automatically closed after 10 minutes
idle time. Giving the password 9999 can also close
the level.


Local Panel Operations
(cont.)