Programmable stages (99), Eight independent stages, Setting groups – Rockwell Automation 865 Differential Protection Relay User Manual

Page 75

Advertising
background image



Protection Functions

3-31

865-UM001A-EN-P – July 2009

Programmable Stages (99)

For special applications the user can built his own protection stages
by selecting the supervised signal and the comparison mode.

The following parameters are available:

Priority

If operation times less than 60 milliseconds are needed
select 10 ms. For operation times under one second 20 ms
is recommended. For longer operation times and THD
signals 100 ms is recommended.

Link

The name of the supervised signal (see table below).

Cmp

Compare mode. ‘>’ for over or ‘<’ for under comparison.

Pick-up

Limit of the stage. The available setting range and the unit
depend on the selected signal.

t

Definite time operation delay

Hyster

Dead band (hysteresis)

NoCmp

Only used with compare mode under (‘<’). This is the limit to
start the comparison. Signal values under NoCmp are not
regarded as fault.

Available Signals to be Supervised by the Programmable Stages

Alarm stages link signals

Task interval

IL1 – IL3, IL1W-IL3W, I’L1W-I’L3W, IL, I’L 100ms

Io, Io2, Iocalc, I’oCalc, I1, I2, I2/I1, I2/In, I’1,
I’2, I’2/I’1, I’2/In, dIL1, dIL2, dIL3

THDIL1, THDIL2, THDIL3

Eight Independent Stages

The relay has eight independent programmable stages. Each
programmable stage can be enabled or disabled to fit the intended
application.

Setting

Groups

There are two settings groups available. Switching between setting
groups can be controlled by digital inputs, virtual inputs (mimic
display, communication, logic) and manually.

There are two identical stages available with independent setting
parameters.