Tcp/ip, External i/o (modbus rtu master) – Rockwell Automation 865 Differential Protection Relay User Manual

Page 142

Advertising
background image

7-16 Communications

865-UM001A-EN-P – July 2009

TCP/IP

Modbus TCP uses TCP/IP protocol. Also SetPointPS and SPA-bus
and DNP 3.0 communication can be directed via TCP/IP.

The IP address, net mask, gateway, name server and NTP server are
common with the internal Ethernet port setting.

Table 7.13 – TCP/IP Parameters

Parameter

Value

Unit

Description

Set

IpAddr

n.n.n.n

Internet protocol address (set with
SetPointPS)

Set

NetMsk

n.n.n.n

Net mask (set with SetPointPS)

Set

Gatew

default = 0.0.0.0

Gateway IP address (set with
SetPointPS)

Set

NameSv

default = 0.0.0.0

Name server (set with SetPointPS)

Set

NTPSvr

n.n.n.n

Network time protocol server (set
with SetPointPS)
0.0.0.0 = no SNTP

Set

Port

502 = default

Port 502 is reserved for Modbus
TCP

Set

Set = An editable parameter (password needed)

External I/O (Modbus RTU master)

External Modbus I/O devices can be connected to the relay using this
protocol. (See “External input/output Module” in Chapter 9 for more
information).

IEC

61850

IEC 61850 protocol is available with the optional 61850 interface.
The protocol can be configured to transfer the same information
which is available with the IEC 103 protocol. When IEC 61850 is
used, the Remote port protocol of the relay is set to IEC-103.