10-10 Technical

Data

865-UM001A-EN-P – July 2009


Table 10.25 –Arc protection stage ArcI

0

> (50AR), option (cont.)

Inaccuracy:
- Starting

10% of the set value

- Operating time

±5 ms

- Delayed ARC light

±10 ms


Table 10.26 – Arc protection stage ArcI

02

> (50AR), option

Setting range

0.5 - 10.0 x I

n

Arc sensor connection

S1, S2, S1/S2, BI, S1/BI, S2/BI, S1/S2/BI

- Operating time (Light only)

13 ms

- Operating time (4xIset + light)

17ms

- Operating time (BIN)

10 ms

- BO operating time

<3 ms

Reset time

<95 ms

Reset time (Delayed ARC L)

<120 ms

Reset time (BO)

<80 ms

Reset ratio

0.90

Inaccuracy:
- Starting

10% of the set value

- Operating time

±5 ms

- Delayed ARC light

±10 ms

Supporting Functions

Disturbance Recorder (DR)

The operation of disturbance recorder depends on the following settings.
The recording time and the number of records depend on the time setting
and the number of selected channels.

Table 10.27 – Disturbance recorder (DR)

Mode of recording:

Saturated / Overflow

Sample rate:
- Waveform recording
- Trend curve recording


32/cycle, 16/cycle, 8/cycle
10, 20, 200 ms
1, 5, 10, 15, 30 s
1 min

Recording time (one record)

0.1 s – 12 000 min
(must be shorter than MAX time)

Pre-trigger rate

0 – 100%

Number of selected channels

0 – 12